AS-Interface power supply VAN-115/230AC-K27

VAN-115/230AC-K27
  • Up to 4 A output load
  • LED operating display
  • 100 V AC up to 240 V AC
  • AS-Interface filter integrated
  • Earth fault detection
 in stock
450.00 USD
Netlist price. Your individual price will be calculated during checkout.
Unit Price 

Quantity

Free Shipping

Purchase on Account

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  VAN-115/230AC-K27

Product Description
AS-Interface power supply, data decoupling, 4 A
General specifications
UL File NumberE223176
MTBF100 a
Indicators/operating means
Reset push-button switchearth fault simulation/reset of earth fault display
LED EFDearth fault display; LED red
LED AS-i okLED green:
ON: AS-Interface voltage OK
OFF: overload or no supply voltage
Electrical specifications
FusingT3A 15/250 V HBC (not accessible)
Rated operating voltage85 … 132 VAC
184 … 264 VAC
240 … 300 VDC
Rated operating current2.7 A at 115 VAC
1.3 A at 230 VAC
Supply frequency47 ... 63 Hz (alternatively, DC possible)
Efficiencytyp. 90 % (230 VAC, 4 A)
Galvanic isolationSELV/PELV
Peak inrush current< 3.7 A2s (120 VAC)
< 4.6 A2s (132 VAC)
< 2.5 A2s (230 VAC)
< 3.3 A2s (264 VAC)
Output
Short-circuit protection/overload> 4,2 A
< 6.5 A
Current limitstarts at > 4.2 A
Voltage30.5 VDC ±3 % fixed
Current4 A
Residual ripple< 50 mVSS (500 kHz bandwidth, 50 Ω measurement, with resistive load)
Voltage limitationlimited to max. 55 V
Compliance with standards and directives
Directive conformity
EMC Directive 2004/108/ECEN 55022:2006, EN 55011:2009 Class B
EN 61000-6-3:2001 , EN 61204-3:2001
Standard conformity
Noise immunityEN 61000-6-2:2005
Emitted interferenceEN 61000-6-3:2007
EN 61000-3-2:2010
EN 61000-3-3:2009
Galvanic isolationIEC 60364-4-41:2005 (PELV)
IEC 60950:1999 (SELV)
Degree of protectionIEC 60529:2001
Pollution degreeEN 50178:1997
Mech. capacityEN 60068-2-6:2008 (Sinus)
EN 60068-2-64:2009 (Random)
Shock and impact resistanceEN 60068-2-27:1995
Ambient conditions
Ambient temperature-10 ... 70 °C (14 ... 158 °F)
note derating
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Shock and impact resistance15g/6 ms
10g/11 ms
Vibration resistanceSine 2 - 17.8 Hz: ± 1.6 mm
Sine 17.8 ... 500 Hz : 2 g
Random 2 … 500 Hz: 0.5 m2 (s³)
Pollution degree2
Mechanical specifications
Degree of protectionIP20
Protection class1 (IEC 60536); Protective conductor connection necessary
ConnectionConnection terminals, max. conductor cross-section
Flexible cable: 0.5 … 4 mm2
Rigid cable: 0.5 … 6 mm2
Stripping length 7 mm
Mass650 g
Dimensions
Height124 mm
Width73 mm
Length102 mm
MountingDIN mounting rail

Classifications

SystemClasscode
ECLASS 13.027040301
ECLASS 12.027040301
ECLASS 11.027040301
ECLASS 10.0.127040301
ECLASS 9.027040301
ECLASS 8.027040301
ECLASS 5.127040301
ETIM 9.0EC002540
ETIM 8.0EC002540
ETIM 7.0EC002540
ETIM 6.0EC002540
ETIM 5.0EC002540
UNSPSC 12.139121004

Details: VAN-115/230AC-K27

Function

The primary switched-mode power supply was designed for fieldbus applications that transfer energy and data together via a two-wire cable
(AS-Interface concept). It supplies a fully extended AS-Interface system with a maximum output current of 4.0 A. Due to the sinusoidal current consumption of the network, harmonics are avoided.

The power supply assumes the function of supplying power, data decoupling for the power source and balancing both output lines
(AS-Interface + and AS-Interface -) with respect to the machine ground (shielded connection). The transformer allows the use of unshielded load cables. The power supply is protected by an internal fuse that eliminates the need for additional device protection measures.

Ground fault monitor GF:

The switch output of the ground fault monitor evaluates any short circuits detected in the AS-Interface system. With the potential-free transistor output, the system can be shut down using the control program. The output is normally closed, but opens when a ground fault is detected. The "GF" LED also signals the presence of a ground fault. This output will close when the power supply is restarted or the reset button is pressed for (> 2 seconds). It is essential to connect the shield to PE or the machine ground to guarantee proper operation.

Checking the ground fault monitor:

Pressing the reset button briefly (< 2 seconds) simulates a ground fault in the device. Detection, evaluation and signaling of a ground fault and the switch output can be tested at suitable intervals. A ground fault generated in this way can be reset by pressing the reset button for (> 2 seconds).

Product Documentation: VAN-115/230AC-K27

Language Selection:
Brief InstructionsLanguageFile TypeFile Size
Instruction leaflet / BeipackzettelALLPDF350 KB

Design / Simulation: VAN-115/230AC-K27

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP2062 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ98 KB

Approvals: VAN-115/230AC-K27

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
US CA ULE223176ALLLINK---
US CA ULCoC E223176 RptRef E223176-20070416ALLPDF444 KB
Worldwide AS-International Association AS-Interface95001ALLPDF389 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-4815AALLPDF164 KB

Associated Products: VAN-115/230AC-K27

Accessories
AS-Interface Power supply and network checking utilityfa