Termination Board HiCTB16-FBM-RAC-SC-AI16

HiCTB16-FBM-RAC-SC-AI16
  • System board for Schneider, Foxboro FBM series
  • For 16 modules
  • For 16-channel AI card FBM211
  • 24 V DC supply
  • Recommended modules: HiC2025(A) (AI), HiC2025ES (AI), HiC2081 (TI)
  • Hazardous area: screw terminals, blue
  • Non-hazardous area: Sub-D connector (male), 37-pin

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Datasheet excerpt: Technical data of  HiCTB16-FBM-RAC-SC-AI16

Supply
ConnectionX20: terminals 3, 5(+); 4, 6(-)
Nominal voltage24 V DC , in consideration of rated voltage of used isolators
Voltage drop0.9 V , voltage drop across the series diode on the termination board must be considered
Ripple≤ 10 %
Fusing4 A , in each case for 16 modules
Power dissipation≤ 500 mW , without modules
Reverse polarity protectionyes
Redundancy
SupplyRedundancy available. The supply for the isolators is decoupled, monitored and fused.
Fault indication output
ConnectionX20: terminals 1, 2
Output typevolt-free contact
Switch behaviourno fault: relay contact closed
power supply fault: relay contact open
module fault: relay contact open
Contact loading30 V DC, 1 A
Indicators/settings
Display elementsLED PWR1 (termination board power supply), green LED
LED PWR2 (termination board power supply), green LED
LED FAULT (fault indication), red LED
- LED lits: module fault
- LED flashes: power supply fault
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2017
For further information see system description.
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Connection
Field sideexplosion hazardous area: 4 screw terminals per module , blue
Control sidenon-explosion hazardous area: Sub-D connector , 37-pin
Supplypluggable screw terminals , black
Fault outputpluggable screw terminals , black
Core cross sectionscrew terminals: 0.25 ... 1.5 mm2 (24 ... 12 AWG)
Materialhousing: polycarbonate, 10 % glass fiber reinforced
Massapprox. 720 g
Dimensions216 x 200 x 163 mm (8.5 x 7.9 x 6.42 inch) (W x H x D) , depth including module assembly
Height200 mm
Width216 mm
Depth163 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateCESI 06 ATEX 022
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Non-hazardous area
Maximum safe voltage250 V (Attention! Um is no rated voltage.)
Galvanic isolation
Field circuit/control circuitsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 50303:2000
International approvals
UL approvalE106378
Control drawing116-0327
IECEx approval
IECEx certificateIECEx CES 06.0003
IECEx marking[Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210120
ECLASS 12.027210120
ECLASS 11.027210120
ECLASS 10.0.127210120
ECLASS 9.027210120
ECLASS 8.027210120
ECLASS 5.127210120
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: HiCTB16-FBM-RAC-SC-AI16

The function of the termination board and the connector pin assignment are exactly fitted to the requirements of the Foxboro FBM system.

The signal is output to the process control system via the system connector.

Information about a missing supply voltage of the isolated barriers is available for the system as a volt-free contact.

Wiring errors from field side will be reported via the same relay contact, if this function is supported by the isolators.

The termination board has a robust glass fiber reinforced plastic housing.

The termination board is mounted in the switch cabinet on a 35 mm DIN mounting rail according to EN 60175.

Datasheet: HiCTB16-FBM-RAC-SC-AI16

DatasheetFile TypeFile Size
Datasheet HiCTB16-FBM-RAC-SC-AI16PDF1514 KB
Fiche de données HiCTB16-FBM-RAC-SC-AI16PDF1522 KB
Datenblatt HiCTB16-FBM-RAC-SC-AI16PDF1518 KB
Datasheet HiCTB16-FBM-RAC-SC-AI16PDF1581 KB
Hoja de datos HiCTB16-FBM-RAC-SC-AI16PDF1521 KB

Documents: HiCTB16-FBM-RAC-SC-AI16

ManualsFile TypeFile Size
System ManualPDF5438 KB
SystemhandbuchPDF5450 KB
Instruction manuals
ИнструкцииPDF162 KB
Instruction manual / BetriebsanleitungPDF317 KB
Návod k poużitíPDF157 KB
Instruktions manualPDF156 KB
Instruction manualPDF161 KB
KasutusjuhendPDF153 KB
KäyttöohjePDF153 KB
Manuel d'instructionsPDF158 KB
BetriebsanleitungPDF162 KB
Οδηγίες χρήσηςPDF165 KB
HandleidingPDF157 KB
Instruction manual / BetriebsanleitungPDF156 KB
Használati útmutatóPDF157 KB
Manuale di istruzioniPDF156 KB
Lietošanas pamācībaPDF156 KB
Instrukciju vadovasPDF157 KB
Instrukcja obsługiPDF158 KB
Manual de instruçõesPDF157 KB
Manual de utilizarePDF157 KB
Návod na poużitiePDF156 KB
Navodila za uporaboPDF155 KB
Manual de instruccionesPDF157 KB
ManualPDF154 KB
Short instructions, safety information
Brief instructionsPDF2805 KB
KurzanleitungPDF2809 KB
Technical information
Pinout TablePDF72 KB

CAD+CAE: HiCTB16-FBM-RAC-SC-AI16

CADFile TypeFile Size
CAD 2-D / CAD 2-DZIP16364 KB

Associated Products: HiCTB16-FBM-RAC-SC-AI16

Matching System Components
1-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 45 mA at 12 V DC, Line fault transparency (LFT), Test pulse immunity, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Line fault transparency, Filter, Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V bus powered via Termination Board
19 ... 30 V loop powered via input , reverse polarity protected, Type: logic inputpa
Accessories
For HiC Termination Boards, 1 piece for 8-position Termination Board, 2 pieces for 16-position Termination Boardpa
1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Low power dissipation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter, Field device [2]: current sourcepa
1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Sink or source mode, Line fault detection (LFD), Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitterpa
1-channel isolated barrier, 24 V DC supply (bus powered), Thermocouple, RTD, potentiometer or voltage input, Linearized output 4 mA ... 20 mA, sink/source, Sensor breakage detection, Configurable by PACTware, Line fault detection (LFD), Up to SIL 2 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC bus powered via Termination Board, Type: 2-wire connection, Type [2]: 3-wire connection, Type [3]: 4-wire connectionpa