Termination Board HiCTB16-TRX-RAC-PL-DI32

HiCTB16-TRX-RAC-PL-DI32
  • System board for Schneider Electric, Tricon CX series by Triconex
  • For 32-channel DI card 3506X
  • For 16 modules
  • 24 V DC supply
  • Recommended modules: HiC2822 (DI), HiC2842 (DI)
  • Hazardous area: pluggable screw terminals, blue
  • Non-hazardous area: ELCO socket, 56-pin

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Datasheet excerpt: Technical data of  HiCTB16-TRX-RAC-PL-DI32

Supply
ConnectionX20: terminals 3, 5(+); 4, 6(-)
Nominal voltage24 V DC , in consideration of rated voltage of used isolators
Voltage drop0.9 V , voltage drop across the series diode on the termination board must be considered
Ripple≤ 10 %
Fusing4 A , in each case for 16 modules
Power dissipation≤ 500 mW , without modules
Reverse polarity protectionyes
Redundancy
SupplyRedundancy available. The supply for the isolators is decoupled, monitored and fused.
Fault indication output
ConnectionX20: terminals 1(+), 2(-)
Output typevolt-free transistor output , not short-circuit protected , not overload protected
Rated voltage30 V DC
Rated current100 mA
Signal levelno fault: (external voltage) - 1 V max. for 100 mA (Tamb = 25 °C (77 °F))
power supply fault/module fault: blocked output (off-state current ≤ 10 µA)
Indicators/settings
Display elementsLED PWR1 (termination board power supply), green LED
LED PWR2 (termination board power supply), green LED
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2017
For further information see system description.
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Degree of protectionIP20
Connection
Field sideexplosion hazardous area: pluggable screw terminals , blue
Control sidenon-explosion hazardous area: ELCO socket, 56-pin
Supplypluggable screw terminals , black
Fault outputpluggable screw terminals , black
Core cross sectionscrew terminals 0.25 ... 2.5 mm2 (24 ... 12 AWG)
Materialhousing: polycarbonate, 10 % glass fiber reinforced
Massapprox. 765 g
Dimensions216 x 200 x 163 mm (8.5 x 7.9 x 6.42 inch) (W x H x D) , depth including module assembly
Height200 mm
Width216 mm
Depth163 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateCESI 06 ATEX 022
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Non-hazardous area
Maximum safe voltage250 V (Attention! Um is no rated voltage.)
Galvanic isolation
Field circuit/control circuitsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 50303:2000
International approvals
UL approvalE106378
Control drawing116-0327
IECEx approval
IECEx certificateIECEx CES 06.0003
IECEx marking[Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210121
ECLASS 12.027210121
ECLASS 11.027210121
ECLASS 10.0.127210121
ECLASS 9.027210121
ECLASS 8.027210121
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: HiCTB16-TRX-RAC-PL-DI32

The function of the termination board and the system connector pin assignment is exactly fitted to the requirements of the Triconex Tricon CX system.

The signal is output to the safety instrumented system via the system connector.

Information about missing supply voltage of the isolated barriers is available for the system at the volt-free transistor output.

Wiring faults from the field side will be reported via the volt-free transistor output, if this function is supported by the isolators.

The termination board has a robust glass fiber reinforced plastic housing.

The termination board is mounted in the switch cabinet on a 35 mm DIN mounting rail according to EN 60175.

Datasheet: HiCTB16-TRX-RAC-PL-DI32

DatasheetFile TypeFile Size
Datasheet HiCTB16-TRX-RAC-PL-DI32PDF1239 KB
Fiche de données HiCTB16-TRX-RAC-PL-DI32PDF1246 KB
Datenblatt HiCTB16-TRX-RAC-PL-DI32PDF1244 KB
Datasheet HiCTB16-TRX-RAC-PL-DI32PDF1302 KB
Hoja de datos HiCTB16-TRX-RAC-PL-DI32PDF1246 KB

Documents: HiCTB16-TRX-RAC-PL-DI32

ManualsFile TypeFile Size
System ManualPDF5438 KB
SystemhandbuchPDF5450 KB
Instruction manuals
ИнструкцииPDF162 KB
Instruction manual / BetriebsanleitungPDF317 KB
Návod k poużitíPDF157 KB
Instruktions manualPDF156 KB
Instruction manualPDF161 KB
KasutusjuhendPDF153 KB
KäyttöohjePDF153 KB
Manuel d'instructionsPDF158 KB
BetriebsanleitungPDF162 KB
Οδηγίες χρήσηςPDF165 KB
HandleidingPDF157 KB
Instruction manual / BetriebsanleitungPDF156 KB
Használati útmutatóPDF157 KB
Manuale di istruzioniPDF156 KB
Lietošanas pamācībaPDF156 KB
Instrukciju vadovasPDF157 KB
Instrukcja obsługiPDF158 KB
Manual de instruçõesPDF157 KB
Manual de utilizarePDF157 KB
Návod na poużitiePDF156 KB
Navodila za uporaboPDF155 KB
Manual de instruccionesPDF157 KB
ManualPDF154 KB
Short instructions, safety information
Brief instructionsPDF3237 KB
KurzanleitungPDF3247 KB
Technical information
Pinout TablePDF140 KB

CAD+CAE: HiCTB16-TRX-RAC-PL-DI32

CADFile TypeFile Size
CAD 2-D / CAD 2-DZIP16364 KB

Approvals+Certificates: HiCTB16-TRX-RAC-PL-DI32

CertificatesFile TypeFile Size
Brasil TUV Rheinland BrazilPDF1284 KB
CESI IECEx Certificate of ConformityLINK---
China SITIIAS CCC Ex CertificatePDF1842 KB
Europe CESI ATEX Category (1) GD ATEX Category (M1)PDF869 KB
India PESO (India) CCOEPDF100 KB
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378PDF478 KB
Control Drawings
Control drawing UL / Control drawing ULPDF166 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)PDF189 KB
EU Declaration of Conformity (P+F)PDF183 KB
EU Declaration of Conformity (P+F)PDF181 KB
EU Declaration of Conformity (P+F)PDF183 KB
EU Declaration of Conformity (P+F)PDF179 KB
EU Declaration of Conformity (P+F)PDF180 KB
EU Declaration of Conformity (P+F)PDF181 KB
EU-Konformitäterklärung (P+F)PDF183 KB
EU Declaration of Conformity (P+F)PDF189 KB
EU Declaration of Conformity (P+F)PDF180 KB
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)PDF181 KB
EU Declaration of Conformity (P+F)PDF182 KB
EU Declaration of Conformity (P+F)PDF180 KB
EU Declaration of Conformity (P+F)PDF180 KB
EU Declaration of Conformity (P+F)PDF183 KB
EU Declaration of Conformity (P+F)PDF184 KB
EU Declaration of Conformity (P+F)PDF182 KB
EU Declaration of Conformity (P+F)PDF181 KB
EU Declaration of Conformity (P+F)PDF183 KB
EU Declaration of Conformity (P+F)PDF180 KB
EU Declaration of Conformity (P+F)PDF180 KB
EU Declaration of Conformity (P+F)PDF180 KB
EU Declaration of Conformity (P+F)PDF182 KB

Associated Products: HiCTB16-TRX-RAC-PL-DI32

Accessories
For HiC Termination Boards, 1 piece for 8-position Termination Board, 2 pieces for 16-position Termination Boardpa
2-channel isolated barrier, 24 V DC supply (bus powered), Dry contact or NAMUR inputs, 2 relay contact outputs, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (NO contact), Fault indication outputpa
2-channel isolated barrier, 24 V DC supply (bus powered), Dry contact or NAMUR inputs, 2 passive transistor outputs, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detectionpa